TN-S是(shi)壹(yi)種(zhong)接地(di)系統(tong)。
TN-S系統(tong)適用(yong)於內(nei)部(bu)設有(you)變(bian)電所的(de)建(jian)築(zhu)物。TN-S系統(tong)電源(yuan)的(de)壹(yi)點(dian)與(yu)大(da)地(di)直(zhi)接(jie)連(lian)接(jie)(T是(shi)“大(da)地(di)”壹(yi)詞(ci)法文(wen)Terre的(de)個字母(mu));
外(wai)露導(dao)電部(bu)分通過與(yu)接(jie)地(di)的(de)電(dian)源(yuan)中(zhong)性(xing)點的(de)連(lian)接(jie)而(er)接地(di)(N是(shi)“中(zhong)性(xing)點”壹詞(ci)法文(wen)Neutre的(de)個字母(mu));
在(zai)全(quan)系統(tong)內(nei)中(zhong)N線(xian)和PE線(xian)是(shi)分開的(de)(S是(shi)“分開”壹(yi)詞(ci)法文(wen)Separe的(de)個字母(mu))。故障(zhang)電(dian)流(liu)通過PE線(xian)來(lai)傳(chuan)導(dao)。
TN-S除(chu)具有(you)TN-C系統(tong)的(de)優(you)點(dian)外(wai),由(you)於正常(chang)時(shi)PE線(xian)不通過負(fu)荷電(dian)流,故與(yu)PE線(xian)相連(lian)的(de)電(dian)氣(qi)設(she)備金屬(shu)外(wai)殼在電(dian)氣(qi)正常(chang)運(yun)行(xing)時不(bu)帶電(dian),所以適用(yong)於數據(ju)處理和(he)精密(mi)電(dian)子(zi)儀(yi)器(qi)設備的(de)供(gong)電(dian),也(ye)可用於爆炸(zha)危(wei)險環(huan)境(jing)中(zhong)。
在(zai)380V低壓配電(dian)網(wang)中(zhong),按(an)接地(di)方(fang)式有(you)三(san)種(zhong)五類:TT、TN-C、TN-S、TN-C-S、IT。
TT系統(tong):根據(ju)《安(an)全技(ji)術規範(fan)》中(zhong),TT系統(tong)指:電源(yuan)側配電(dian)變壓(ya)器(qi)中(zhong)性(xing)點直接接(jie)地(di),負(fu)荷側(ce)設備不帶(dai)電的(de)金(jin)屬(shu)外(wai)殼直接(jie)與(yu)大(da)地(di)連(lian)接(jie),但(dan)與電(dian)源(yuan)側配電(dian)變壓(ya)器(qi)中(zhong)性(xing)點沒有(you)直(zhi)接電氣(qi)連接。
TN系統(tong):根據(ju)《安(an)全技(ji)術規範(fan)》中(zhong),TN-S、TN-C、TN-C-S系統(tong)指:電源(yuan)側配電(dian)變壓(ya)器(qi)中(zhong)性(xing)點直接接(jie)地(di),負(fu)荷側(ce)設備不帶(dai)電的(de)金(jin)屬(shu)外(wai)殼與變(bian)壓(ya)器(qi)中(zhong)性(xing)點有(you)直(zhi)接電氣(qi)連接。這三(san)類系統(tong)中(zhong)區(qu)別(bie)是(shi):TN-S零(ling)線(xian)和保(bao)護零(ling)線(xian)(地(di)線(xian))是(shi)分開的(de)。TN-C零(ling)線(xian)和保(bao)護零(ling)線(xian)是(shi)共(gong)用的(de)。 TN-C-S零(ling)線(xian)和保(bao)護零(ling)線(xian)部分共(gong)用,部(bu)分分開。
IT系統(tong)是(shi)三(san)相三(san)線(xian)式接(jie)地(di)系統(tong),該系統(tong)變壓器(qi)中(zhong)性(xing)點不接地(di)或(huo)經(jing)阻(zu)抗(kang)接地(di),無中(zhong)性(xing)線(xian)N,只有(you)線(xian)電壓(ya)(380V),無相電(dian)壓(ya)(220V),保(bao)護接(jie)地(di)線(xian)PE各(ge)自(zi)獨立接地(di)。該(gai)系統(tong)的(de)優(you)點(dian)是(shi)當(dang)壹相接(jie)地(di)時(shi),不(bu)會(hui)使(shi)外(wai)殼帶有(you)較(jiao)大(da)的(de)故障(zhang)電(dian)流(liu),系統(tong)可以照常(chang)運(yun)行(xing)。缺點是(shi)不(bu)能配出(chu)中(zhong)性(xing)線(xian)N。因此(ci)它(ta)是(shi)不(bu)適用(yong)於擁有(you)大(da)量單相(xiang)設(she)備的(de)智(zhi)能化(hua)大(da)樓的(de)。